- CLW has 6 nos 1750 KW DG sets for emergency power supply. The power packs are provided with EGB - 13 P type engine governor. These governors have been suggested to be replaced by PG type EM governor ( such as that of M/S Woodward).
- DG 4 in CPH ( !987) is to be condenmed. CEE has lready approved. Survey could not be finalised for want of copper content.
- DG 5 ( 1995 ) in CPH is shut down since 2004 for want a pedestal bearing ( BHEL ) of AVR with brush and separate excitation.
- DG-2 (1978) is shut down since last 1 month due to 11 KV cable fault.
- Recently Jamalpur workshop has given quotation for IOH ( M-48) and POH (M-96).
33 KV power supply is taken at MSS from DVC and fed to main workshop , TM, Steel Foundary, Township and Water Supply through one 12 MVA transformer, three 10 MVA transformer and one 6 MVA transformer.PF is maintained at 0.94. There are 42 outdoor type and 21 indoor type ( 11/0.4) sub stations.One 3.3 KV Sidhabari substation serves pump house. यह ब्लॉग चित्तरंजन के पावर सप्लाई सिस्टम और तकनीकी बारीकियों के बारे में चर्चा का माध्यम है.